| Type: | Smoke Sensor Probe |
|---|---|
| Types of Smoke Detectors: | Photoelectric Smoke Style |
| Product Name: | 4 Wire Photoelectric Duct Smoke Detector |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
|
Physical Specifications
|
|||
|
Size:
(Rectangular Dimensions)
(Square Dimensions) |
7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth
|
||
|
Weight
|
About 1.5kg
|
||
|
Operating Temperature Range
|
-4° to 158°F (-20° to 70°C)
|
||
|
Storage Temperature Range
|
-22° to 158°F (-30° to 70°C)
|
||
|
Operating Humidity Range
|
0% to 95% relative humidity non-condensing
|
||
|
Air Duct Velocity
|
100 to 4,000 ft/min (0.5 to 20.32 m/sec)
|
||
|
Electrical Ratings
|
|||
|
Power Supply Voltage
|
20-29 VDC
|
24 VAC 50-60 Hz
|
240 VAC 50-60 Hz
|
|
Input Capacitance
|
270 µF max.
|
270 µF max.
|
N/A
|
|
Reset Voltage
|
3.0 VDC min.
|
2.0 VAC min.
|
20 VAC min.
|
|
Reset Time (with RTS451)
|
.03 to 0.3 sec.
|
.03 to 0.3 sec.
|
.03 to 0.3 sec.
|
|
Reset Time (by power down)
|
0.6 sec. max.
|
0.6 sec. max.
|
0.6 sec. max.
|
|
Power Up Time
|
35 sec. max.
|
35 sec. max.
|
35 sec. max.
|
|
Alarm Response Time
|
15 sec.
|
15 sec.
|
15 sec.
|
|
Sensitivity Test
|
See detector label
|
See detector label
|
See detector label
|
|
Current Requirements: (using no accessories)
|
|||
|
Max. Standby Current
|
21 mA @ 24 VDC
|
65 mA RMS @ 24 VAC 60 Hz
|
10 mA RMS @ 240 VAC 60 Hz |
|
Max. Alarm Current
|
65 mA @ 24 VDC
|
135 mA RMS @ 24 VAC 60 Hz
|
18 mA RMS @ 240 VAC 60 Hz |
|
Contact Ratings
|
|||
|
Alarm Initiation Contacts (SPST) |
2.0 A @ 30 VDC (resistive)
|
||
|
Alarm Auxiliary Contacts
(DPDT)
|
10A@30VDC (resistive); 10A@250VAC (resistive); ½ HP@240 VAC ; ¼ HP@120 VAC
|
||
|
Supervisory Contacts
(SPDT)
|
2.0 A @ 30 VDC (resistive); 2.0 A @ 125 VAC (resistive)
|
||